Air bottle Regulations,Air bottle Mountings, Air bottle Internal Surface Coatings And Safety Devices on Main Air bottle

SOLAS Air receiver Regulations
» Total capacity of air receivers must be sufficient to give at least 12 starts for reversible engine, and at least 6 starts for non-reversible engine, without refilling the receivers.
»There must be two identical main air receivers and one emergency bottle for every vessel. 
Mountings in Air Receiver:
>Fusible plug
composition – Bismuth 50%, Tin 30%, Lead 20%,
Melting point: 220F (104.4C). Fitted at the reservoir's bottom or on reservoir at ship side
>Atmospheric relief valve:-Provided for back-up of fusible plug. In case of ER fire when 
CO2 flooding is required, this valve is opened before evacuating ER
.
>Spring loaded safety valve:
          Setting pressure:32 bar (for 30 bar working pressure),with 10% rise in 
accumulation of pressure. May be fitted directly or with extension
>Compensation ring: When a hole is cut or machined in pressure vessel, 
higher stresses will subject to the material around the hole, and to reduce this,compensation rings are fitted. 
It is a flange on which a valve or fitting is usually mounted. 


>Manual Drain valve or Automatic Drain valve
>Pressure gauges
>Access doors
>Main starting air valve, auxiliary starting air valve, filling valve, service air or whistle air valve

Internal surface coating:
Graphite suspension in water,Linseed oil, Copal vanish or Epoxy coating having basic properties of anti-corrosive,anti-toxic or anti-oxidation.
Safety devices on Main Air Bottle:
>Fusible plug.
>Pressure Relief Valve
>Atmospheric Relief Valve.
>Low Air Pressure alarm.
>Automatic or remote control Moisture Drain Valve


>>All credits goes to Facebook group 
        If you have any quires comment below

3 Comments


>> Your Comments are always appreciated...
>> Discussion is an exchange of knowledge It Make the Mariner Perfect.... Please Discuss below...

  1. Thank you so much...all of your cooperation is highly appreciated..๐Ÿ™‚๐Ÿ™‚๐Ÿ™‚๐Ÿ™‚

    ReplyDelete
  2. Please advise the number of SOLAS Regulation regarding:

    SOLAS Air receiver Regulations
    » Total capacity of air receivers must be sufficient to give at least 12 starts for reversible engine, and at least 6 starts for non-reversible engine, without refilling the receivers.

    ReplyDelete
    Replies
    1. It is a Class requirement. (IACS UR M61)
      Regards

      Delete
Previous Post Next Post