SOLAS Regulation For Fire Detection System

 Fixed fire detection and fire alarm system should have,

> Manually operated call points shall be capable of immediate operation

> Not be used for any other purpose, except that closing of fire doors

> Suitably designed to withstand supply voltage variation and transients, ambient temperature changes, vibration, humidity, shock, impact and corrosion normally encountered in ships

> Capacity to ensure that any fault occurring in the loop will not render the whole loop ineffective

> Capable of restoring initial configuration in case of power failure

> No loop shall pass through same space twice 

> Two power sources

> Suitable instructions and component spares for testing and maintenance shall be provided

Heat Detectors

> Max floor area per detector: 37 m2

>  Max distance apart between centre: 9 m

>  Max distance away from bulkhead: 4.5 m

Smoke Detectors

> Max floor area per detector: 74 m2

> Max distance apart between center: 11 m

> Max distance away from bulkhead: 5.5 m